Code of air conditioner error, Daikin air conditioner: How to check and diagnose
How to check and diagnose the error code of Daikin air conditioner below will help you to be able to actively grasp the problem situation that the device encountered. Since then, there will be timely and prompt solutions to not affect the efficiency and durability of the machine.
Check and diagnose Daikin line of SkyAir air conditioner fault codes (Air conditioner) and VRV (Central air conditioner)
For wired remote control
Control line BRC1C62
- If the device stops operating due to a problem, the LED on the control will blink and the trouble code is displayed.
- Or even if the machine stops working, the trouble code will be displayed when you conduct the test as follows: Press ON / OFF for 4 seconds or more when the incident history will be deleted. The trouble code will flash and the operation mode will switch from check to normal.
Control BRC1E62
- If the machine stops working due to a problem, the display on the control will blink. The words 'Error: Press Menu button' or 'Error' appear.
- You press the Menu / Enter button, then the error code will be displayed
For wireless remote control
If the machine stops working due to a problem, the LED indicator works on the light signal receiver. To know the error code you do this by following:
1. Press the INSPECT / TEST button to select "check."
2. The device will start the test mode. The indicator 'Unit' and 'Unit No' flashes the number '0'. Press UP or DOWN button and change display number of indoor unit until there is a sound from the indoor unit.
- If there is a beep: Follow steps 3 and 4 below
- If there are 3 beeps: Perform all the steps below
3. Press the MODE button. The number '0' to the left (the first character) displays the flashing error code
4. Diagnose the first character of the trouble code. Press UP or DOWN button to change the first character of
trouble code until the cry comes out:
- Extended beep:: The first and last characters of the problem match. (Incident code is confirmed)
- 2 short beeps: Initial character breakdown
- 1 short beep: Last character of the match
5. Press the MODE button. The number '0' on the right (the following character) displays the flashing incident code
6. Diagnose the following character of the trouble code. Press the UP or DOWN button to change the incoming characters
when the cry comes out. The number of times the beep sounds like step 4.
Check and diagnose Daikin line RA air conditioner fault codes (Civil air conditioning)
Control ARC447A
- Control direction towards the indoor unit and press and hold the CANCEL button for 5 seconds
- The temperature display on the remote control changes to the display of the error code and a long beep announces this change.
- To delete, display the error code you press and hold CANCEL for 5 seconds or they will automatically exit the mode if you do not execute the command within 1 minute
Control ARC455A, ARC452A, ARC433B, ARC423A, ARC417A
Method 1:
- Press and hold the 'Cancel' button for 5 seconds, the '00' code will display on the monitor screen at the temperature display position.
- Repeat pressing the 'Cancel' button continuously until there is a long beep
- To clear the display of the trouble code, press and hold the 'Cancel' button for 5 seconds. Or the error code display screen will automatically exit the test mode after 1 minute without pressing the next button.
Method 2:
1. Press 3 buttons (TEMP, TEMP, MODE) simultaneously to switch to test mode.
2. Press the TEMP button up or down to change this number when you hear the "beep" or "pi" sound
pi ".
- 1 short beep: The tens of numbers do not correspond to the incident code.
- 2 short beeps: The number of tens matches the trouble code but the unit number is not.
- 1 long beep: Both the tens and unit numbers match the trouble code
3. Press the MODE button. Number of units flashing.
4. Press the TEMP button up or down to change this number until you hear a long "beep". The beep sounds like step 2.
5. Determine the problem code. The number displayed when you hear a long 'beep' is the problem code.
6. Press the MODE button to exit the diagnostic mode. Displaying '7' is a test mode notification
7. Press the ON / OFF button twice to return to normal mode.
Note: When not used for 60 seconds, the remote control will return to normal mode.
Code of air conditioner error, air conditioner Daikin line Skyair, VRV, RA most common
Daikin air conditioner error codes with outdoor unit
1. E0 error code
Error name: Activate protection device (uniform)
Presumptive cause: The external protective device connecting the outdoor unit board is activated. Liquid connection with external protective devices
2. E1 error code
Fault name: Error on the outdoor unit circuit
False cause: The outdoor unit board is damaged. The internal / external relay connection cord is faulty
3. E3 error code
Fault name: High-voltage switch drive (HPS)
Presumptive cause: The outdoor heat exchanger is dirty. High voltage switch is faulty. Switch gas pipes. Connection errors
4. E3 error code
Fault name: Digital system 1. Drive of high pressure switch (HPS)
Presumptive cause: The outdoor heat exchanger is dirty. Lack of water. Switch gas pipes. Connection errors. HPS has an error
5. E4 error code
Fault name: Drive of low pressure switch (LPS)
Hypothesis: Hypotension decreases abnormally. Low voltage sensor fault. The outdoor unit board is damaged. Connection errors
6. Error code E5
Error name: Inverter compressor motor error or overheating
Presumptive cause: Inverter compressors get stuck. High differential pressure. Inverter board failed. Connection errors
7. E6 error code
Fault name: STD compressor too line / mechanical jam
False cause: Compressor is faulty. Controller board is faulty. Unblock valve
8. E6 error code
Fault name: Digital system 1. STD compressor over current / mechanical jam
False cause: Electronic throttle valve fails. Lack of refrigerant. Compressor failed
9. E7 error code
Fault name: Outdoor unit fan motor error
Presumptive cause: Fan motor error. The connection between the board and the fan motor is loose or loose. Fan stuck
10. E8 error code
Error name: Excess inverter compressor line
False cause: Compressor is faulty. The inverter electrolytic capacitor fails. The circuit of the outdoor unit is faulty. Power transistor failed
11. E9 error code
Error name: Electronic throttle valve error
False cause: Electronic connection error. Electronic throttle valve failed. The control unit of the outdoor unit is faulty
12. ER error code
Error name: Four-way valve fault or hot / cold switch
False cause: Four valves are faulty. Lack of gas. Bo outdoor unit is faulty. Temperature sensor failed
13. EC error code
Error name: Water temperature enters the outdoor unit abnormally
Presumptive cause: Abnormal cooling water temperature. The circuit of the outdoor unit is faulty. Temperature sensor failed
14. F3 error code
Error name: Push head temperature error
Presumptive cause: The sensor head temperature is damaged. Abnormal head temperature. The control board of the outdoor unit is damaged. Connection errors
15. F6 code error
Fault name: Unusually high pressure or refrigerant excess
Cause of presumption: Gas overcharge. Loss of the heat exchanger temperature sensor connection. Lost connection of the hot air return unit temperature sensor. Loose connection of liquid pipe temperature sensor. Bo outdoor unit is faulty
16. H0 error code
Error name: Error sensor system of the compressor
Presumptive cause: The connection cord is loose or loose. The board is defective
17. H1 error code
Fault name: Room temperature sensor error or humidifier damper
False cause: The limit switch is faulty. Damper fails
18. H3 error code
Fault name: High-voltage switch fault (HPS)
Presumptive cause: High-voltage switch is faulty. Connection wire error. The circuit of the outdoor unit is faulty. Connection error
19. H4 error code
Fault name: Low voltage switch fault (LPS)
False cause: The pressure switch is faulty. Connection wire error. The circuit of the outdoor unit is faulty. Connection error
20. H5 error code
Error name: Overload sensor error of compressor motor
Presumptive cause: Thermal sensor overloaded compressor motor is damaged. Connection error
21. H6 error code
Error name: Position protection sensor error
Presumptive cause: Compressor connection error or compressor power supply cable. Compressor is broken. The outdoor unit is broken
22. H7 error code
Fault name: Error in the outdoor unit fan motor signal
False cause: Unusual signal from fan motor (Circuit error). Loss of connection / short circuit of fan motor or connector error. Drive inverter is damaged
23. H8 error code
Error name: Error of compressor thermostat (CT)
Presumptive cause: Power transistor is broken. Reactor is damaged. Wire error connecting the inverter system. The outdoor unit is broken
24. H9 error code
Fault name: External air temperature sensor error
Outdoor
Presumptive cause: Temperature sensor connection error. The outdoor unit is broken. The wind temperature sensor outside the outdoor unit is damaged
25. HC error code
Fault name: Water temperature sensor error (hot)
Presumptive cause: Temperature sensor connection error. The outdoor unit is broken. The water temperature sensor is damaged
26. HF error code
Error name: Warning heat storage device
or storage control
Cause of presumption: Error wire connecting heat storage. Installation error. Exceeds the number of heat storage tanks
27. HJ error code
Fault name: Error in water storage tank temperature
False cause: Low water level. Error setting switch. Water level sensor is defective. Connection error
28. J1 error code
Error name: Error on pressure sensor
Presumptive cause: Connect faulty pressure sensor. Pressure sensor is damaged. The outdoor unit board is damaged
29. J2 error code
Error name: Compressor line sensor error
Presumptive cause: The variable is broken. Compressor is broken. The outdoor unit board is damaged
30. J3 error code
Fault name: Push head temperature sensor error
Presumptive cause: Error with sensor connector. The temperature sensor of the pushhead is damaged. The outdoor unit is broken
31. J4 error code
Error name: Corresponding low temperature saturation sensor error
Presumptive cause: Error with sensor connector. The sensor is damaged. The outdoor unit is broken
32. Error code J5
Fault name: Gas temperature sensor error returned
hot
Presumptive cause: Error with sensor connector. Gas temperature sensor is damaged. The outdoor unit is broken
33. Error code J6
Error name: Exchanging temperature sensor error
heat
Presumptive cause: Error with sensor connector. The temperature sensor of the heat exchanger is damaged. The outdoor unit is broken
34. Error code J7
Error name: Temperature sensor error (Gas circuit)
Presumptive cause: Error with sensor connector. Liquid gas temperature sensor is damaged. The outdoor unit is broken
35. J8 error code
Error name: Temperature sensor error (Gas circuit)
Presumptive cause: Error with sensor connector. Liquid gas temperature sensor is damaged. The outdoor unit is broken
36. J9 error code
Error name: Temperature sensor error (Gas circuit)
Presumptive cause: Error with sensor connector. Gas temperature sensor is slightly damaged. The outdoor unit is broken
37. Error code JR
Error name: Error on high-pressure sensor
False cause: Error in connection. The low voltage sensor is mistakenly connected to the high-pressure sensor position. High pressure sensor is damaged. The outdoor unit is broken
38. JC error code
Error name: Error on high-pressure sensor
False cause: Error in connection. The high-pressure sensor mistakenly connects to the low-pressure sensor position. Low pressure sensor is broken. The outdoor unit is broken
39. JE error code.
Fault name: Oil pressure sensor sensor or sub tank temperature error
False cause: Error in connection. The tank temperature sensor is damaged or the outdoor unit is damaged
40. JF error code
Fault name: Oil level sensor error or heat exchanger frame temperature
False cause: Error in connection. The temperature sensor is broken. The outdoor unit is broken
41. L0 error code
Error name: Error on inverter system
Presumptive cause: Lack of power supply capacity. The power transistor is broken. The outdoor unit is broken
42. Error code L1
Error name: Inverter board error
Presumptive cause: Compressor power supply error. The outdoor fan motor is damaged. Fuse breaker Or inverter board is damaged
43. Error code L3
Error name: Electric box temperature increases
Presumptive cause: The temperature of the radiator wings increases due to wind. The outdoor fan motor is damaged. The power transistor is broken. The outdoor unit is broken
44. Error code L4
Error name: The temperature of the outdoor unit's radiator temperature increases
Presumptive cause: The temperature of the radiator wings increases due to wind. The temperature sensor of the fins is damaged
45. Error code L5
Error name: Overcurrent inverter motor (DC output)
Presumptive cause: Compressor coil error (Breaking the wire or insulation is not guaranteed
told. Compressor does not start (Mechanical jam). Drive inverter is damaged
46. Error code L6
Error name: Overcurrent inverter compressor motor (AC output)
Cause of presumption: Refilling of refrigerant. Lack of power supply capacity. Compressor is broken. Inverter device error
47. L8 error code
Error name: Error in the inverter compressor line
Presumptive cause: Compressor overload. Error of compressor coil. Loss of compressor power cord connection. Drive inverter is damaged
48. Error code L9
Error name: Inverter compressor startup error
Cause of presumption: Service valve is not opened. Compressor is broken. Error connecting compressor power cord
Pressure difference before compressor starts. Drive inverter is damaged
49. Error code LR
Error name: Power transistor error
Presumed cause: Source transistor is damaged. Compressor is broken. The outdoor unit inverter board is damaged
50. LC error code
Fault name: Signal transmission error between the control board and the drive board
False cause: Connection error between the control board and inverter board. External factors (eg noise). Inverter compressor is damaged. Control board is broken (No signal can be transmitted)
51. Error code M1
Error name: Error of the central control board
False cause: The central control board is damaged
52. Error code M8
Fault name: Error connecting signal between other central control devices
Presumptive cause: Loss of other central control equipment. The reset button of the central control is turned on. Signal transmission error. Change the address of the central control
53. MR error code
Error name: Control devices for the central control are not compatible
Presumptive cause: Control devices for central control are not compatible. There is more than one main control. Incorrect installation of central control. The center console is broken
54. MC error code
Error name: Duplicate address, wrong settings
Presumptive cause: The same address as the central control
55. Error code P0
Error name: Lack of refrigerant
Cause of hypothesis: Lack of a cold substance. Switches the piping
56. Error code P1
Fault name: Phase voltage is not balanced, bo error
inverter circuit
Presumptive cause: Phase loss. The voltage is not balanced between phases. Main circuit capacitor error. Main circuit connection error error. Drive inverter is damaged
57. Error code P2
Fault name: Stop the automatic loading operation
Cause of presumption: Service valve is not opened. The valve of the refrigerant medium has not been opened
58. Error code P3
Error name: Electric box temperature sensor error
Presumptive cause: Temperature sensor connection error. The reactor temperature sensor is damaged. Drive inverter is damaged
59. Error code P4
Fault name: Error in the temperature of the fins temperature sensor
Presumptive cause: The temperature sensor of the fins is damaged. Drive inverter is damaged. Inverter compressor is damaged. Fan motor failed
60. Error code P8
Fault name: The anti-ice protection device activates during automatic loading process
Presumptive cause: Close the valve of the refrigerant container.
61. Error code P9
Fault name: Fan motor error (Humidifier device)
False cause: Fan motor is damaged. The outdoor unit is broken. The relay wire is broken. Connection error
62. PR error code
Fault name: Liquid medium during automatic loading process
Presumptive cause: The average tank of the master orchestra is gone
63. PR error code
Fault name: Heating wire broken (Moisture control device)
False cause: The heater is broken. The temperature sensor is damaged. The outdoor unit is broken
64. PC error code
Error name: Out of the substance in the bottle during the automatic loading process (Replace new tank)
Presumptive cause: The medium of the Slave 2 system has been exhausted
65. PH error code
Error name: Out of the substance in the bottle during the automatic loading process (Replace new tank)
False cause: The heater is broken. Connection error. The temperature sensor is damaged. The outdoor unit is broken
66. PJ error code
Fault name: Power installation error (Bo outdoor unit)
Presumptive cause: No installation of power installation components. Wrong settings. The outdoor unit is broken
67. PJ error code
Error name: Control fan and inverter incompatible
Hypothesis causes: The circuit is not suitable. Wrong settings after replacing the outdoor unit board
Daikin air conditioner error code table with indoor unit
1. Error code R0
Error name: Activate peripheral protection device
Presumptive cause: The external protective device connected to the T1-T2 terminal of the indoor unit is activated
2. R1 error code
Fault name: Error on indoor unit circuit
Presumptive cause: The cold frame circuit is damaged. External factors (noise, etc.)
3. R3 error code
Fault name: Error on indoor unit drain system
Presumptive cause: Switching drain pipe, discharge pipe is not enough slope . Pumping discharge is damaged. Float switch has fault or short circuit connection
4. R4 error code
Error name: Error in stone protection
False causes: Lack of water. Low water temperature setting. Water temperature sensor is damaged
5. Error code R5
Fault name: High pressure control in heating mode, controlling ice protection in cooling mode
Presumptive cause: Switch the air filter to the indoor unit or wind. The temperature sensor of the indoor unit heat exchanger is damaged
6. Error code R6
Fault name: Fan motor error
Presumptive causes: Break the wire, short circuit, or loose the fan motor wire connection. Fan motor failed. Error on indoor unit circuit
7. Error code R7
Fault name: Motor wind flap error
The cause of the assumption: The motor of the flap is faulty. Error on indoor unit circuit. Loose wire connection. The flap switch is faulty
8. R8 error code
Error name: Error in AC voltage or over current
Presumptive cause: Level voltage error. Signal line transmission error. Error connecting wires
9. R9 error code
Error name: Electronic throttle valve error
Cause: Faultless coil from the indoor unit is faulty. The chiller board is faulty. The relay cable is faulty
10. RR error code
Error name: Heating system is overheated
Presumed cause: 26WH is activated '
11. Code of RF error
Error name: Error in humidification system
Presumptive cause: A humidifier (optional accessory) leaks. Drainage pipe error (Not enough slope, .). The chilled board is broken
12. RH error code
Fault name: Air filter dust collector error
Presumptive cause: Dust collector error. The insulation is rusty. High voltage error. The chiller board is faulty
13. RJ error code
Error name: Error on setting up the indoor unit board capacity
Presumptive reason: No suitable power installation components have been installed when replacing the new board. The chiller board is faulty
14. Code of C1 error
Fault name: Error connecting the signal between the indoor unit board and the auxiliary board
Presumptive cause: Connection error between the indoor unit circuit boards
15. C4 error code
Fault name: Liquid gas sugar temperature sensor error
False causes: Liquid gas sugar temperature sensor fails. Strange circuit boards
16. C5 error code
Fault name: Gas line temperature sensor error
Hypothetical causes: Gas sugar temperature sensor is slightly damaged. The chilled board is broken. Connection error
17. C6 error code
Fault name: Fan motor sensor error or fan control
False cause: The fan board is damaged. Liquid connection resistor capacity. Wrong settings
18. C7 error code
Fault name: Motor reversing error, limit switch
Hypothetical cause: Motor reversal error. Limit switch error
19. C9 error code
Fault name: Air feedback temperature sensor error
Hypothetical cause: The temperature of an air reversal temperature sensor is damaged. The chilled board is broken. Connection error
20. CR error code
Fault name: Wind temperature sensor error out
Presumptive cause: The wind temperature sensor is damaged. The chilled board is broken. Connection error
21. CC error code
Error name: Humidity sensor error
Hypothetical cause: The humidity sensor fails. Connection error
22. CJ error code
Error name: Temperature sensor error at control
Presumptive cause: The temperature sensor at the control is damaged. The control board is damaged. External factors (noise, etc.)
Above is the error code air conditioner, Daikin air conditioner details, most commonly used today. Hope they will be useful for you to help you easily detect and fix problems.
You should read it
- Panasonic air conditioner error code, air conditioner: How to check and diagnose
- 5 Reasons you should buy Daikin air purifier right away to protect your family's health
- How to check and identify the air conditioner error code, the fastest Electrolux conditioner
- Decode in detail the meaning of the air conditioner code, Nagakawa air conditioner
- Learn the most common Mitsubishi air conditioner fault codes
- Instructions for reading code of air conditioner, Casper air conditioner for quickest repair
- Samsung Air Conditioning, Air Conditioning Code: How to check and diagnose
- Air conditioner error code, Funiki air conditioner and common error handling
- The cause of error codes and failures on air conditioning, air conditioning Sumikura
- How to convert degrees F to degrees C air conditioning, air conditioning on the control
- Midea means the most common air conditioning and air conditioning codes
- Instructions for fixing device Usb error not recognized Code 43
Maybe you are interested
Top 10 fastest running dogs in the world How to turn off the router's SSID for better security Microsoft announced some notable new features on the Outlook for iOS app 26 Dalai Lama's immortal philosophy Overwhelmed with 10 world famous giant Buddha statues A simple trap can kill quickly, compact 4,000 mosquitoes every night anyone can do it at home